TTSIM-2
Leak Detection Module
The
TTSIM-2
sensor interface module monitors up to 150 meters (500 feet) of TraceTek sensing cable. When liquid is detected, the TTSIM-2 unit indicates the leak, displays the location of the leak and switches a relay to provide local voltage-free contact closure. The TTSIM-2 can also communicate to a host monitoring system such as TraceTek TTDM-128 or directly to a PLC or other host system using standard protocols. The low cost of the TTSIM-2 makes it economical to build very robust systems with many small independent sensing cable segments. No field calibration is required
FEATURES
- Voltage-free contacts for alarm signaling.
- LEDs to indicate power, leak, cable trouble, and communication status.
- Leak location display on LCD.
- Simple twisted pair serial RS-485 communications up to 1200 meters (4000 feet) with automatic protocol selection (MODBUS, Opto 22 and Metasys).
- Available for 24, 120 or 230 Vac 50/60 Hz or 12 or 24 Vdc power supply.
- Each TTSIM-2 unit has a unique address assigned with software – no switches.
- Relay software selectable for normally energized or normally de-energized operation.
- DIN rail mounted for easy installation.
- Selectable unit of measure (feet or meters).
- Enclosures available for stand-alone indoor or outdoor installations.
Operating voltage | 22 to 26 Vac, 3 W 12 Vdc +/– 10%, 2 W |
92 to 132 Vac, 3 W 24 Vdc +/– 10%, 2 W |
216 to 253 Vac, 3 W |
Operating temperature | 0°C to 50°C | ||
Operating humidity | 5% to 95% non-condensing | ||
Communication protocol | Modbus®, OptoMux™ or Johnson Controls Metasys™ | ||
Network configuration | RS-485 two wire network, 9600 baud, addressable from 1 to 127 | ||
Maximum length of sensing cable | 150 m (5000 ft) | ||
Precision | 0.5% of sensor length ± 0.6 m (2 ft) | ||
Dimension | 86 x 70 x 58 mm |
TTSIM-2 Product Overview | 12/03/19 |
TTSIM-2 Installation Manual | 12/03/19 |
TTSIM-1A Physical Layout