GS-LDA-2
Water Leak Detection System
The
GS-LDA-2
Sensor Interface Module monitors up to 1500 meters of GuardSen sensing cable (GS-LDC-2). When liquid is detected, the GS-LDA-2 unit indicates the leak, displays the location of the leak and switches a relay to provide local voltage-free contact closure.
The GS-LDA-2 can be used as standalone leak detection alarm unit or can also communicate to a host monitoring system such as PLC or other monitoring systems by using standard RS-485 protocols.
The low cost of the GS-LDA-2 makes it economical to build very robust systems with many small independent sensing cable segments. No field calibration is required.
DESIGN FEATURES
- LEDs to indicate power, leak, and communication status
- Voltage-free contacts for alarm signaling
- Leak location display on LCD
- Standard twisted pair serial RS-485 communications up to 1200 meters (4000 feet) with Modbus protocol
- 12Vdc power supply
- Each GS-LDA-2 unit has a unique address assigned with software – no switches
- Built-in buzzer (85dB)
- DIN rail mounted for easy installation
General Features
Cable compatibility | GuardSen Sensing Cable (GS-LDC-2) |
Maximum length of sensing cable | 1500 m |
Precision | 0.5% of sensor length ± 0.5 m |
Environmental Ratings
Storage temperature | –18°C to 60°C (0°F to 140°F) |
Operating temperature | -20°C to 50°C |
Humidity | 5% to 90% non-condensing |
Power Requirements
Voltage Operating | 12Vdc +/- 10%, 2 W |
Serial Interface
Network configuration | RS-485 two wire network, 9600 baud, addressable from 1 to 127 |
Communication Protocol | Modbus® 485 |
Relay Contacts
Type | Form C (SPDT); Normally close (NC) or Normally open |
Rating | (NO) DC12V, 2A |
GS-LDA-2 Locating Module | 09/17/19 |
GS-LDA-2 Connection
GS-LDA-2 Physical Layout